Hey there! Thanks for reaching out. I'm excited for you! To answer your question, yes the breaker size will definitely be inspected and most likely wire size that matches the breaker limits. Also where wiring is exposed that it is properly weatherproofed with conduit. One thing to note there is its against NEC to run low voltage and high voltage in the same conduit so keep that in mind. Disconnect or breaker should be within 6' of the condensing unit. Also no wiring going into the furnace without some sort of bushing to protect it from rubbing through the wire insulation. More than likely, they will want to make sure the unit is the proper distance from electrical panels and gas meters. So check your installation guide on that for proper distancing. For your furnace, probably the following: Sediment trap (drip leg) Updated quarter turn shutoff valve Approved flexible connector Proper distance on your exhaust venting depending on if it is an 80% or 96% furnace These are the main things, but each inspector is different. I literally had an inspector once say, "so show me what we are looking at here" haha i really had to bite my tongue and not say "well you see, these air DUCTS and air flows through them" 😅🤦🏻♂️ If you do everything properly i'm sure you will be fine, and worst case if you need to change something, you can. Hope this helps! Maybe some others will chime in on their experience with inspections. Best, Dave