Activity
Mon
Wed
Fri
Sun
Jun
Jul
Aug
Sep
Oct
Nov
Dec
Jan
Feb
Mar
Apr
What is this?
Less
More

Memberships

Functional Safety Play Book

258 members • Free

The Academy

5.5k members • Free

1 contribution to Functional Safety Play Book
IEC 61511 - FSA Stage 5 - Modification
Hi all, With regards to carrying out an FSA 5 assessment, is it deemed necessary to carry one out if you are only adding new SIFs into an existing Safety Logic Solver. In this example, the new SIF to be installed does not share any of the same elements (other than the logic solver) as any existing SIF's, and also the new SIF has no impact on any existing SIFs? My thoughts are no, but just wondering if anyone else can clarify if I am correct?
1 like • 28d
Correct, adding a new SIF should go through the FSA lifecycle (1 to 3) and any modifications to an existing SIF go through an FSA5.
1-1 of 1
Lee Johnson
1
4points to level up
@lee-johnson-8017
Electrical & Instrumentation Design Engineer

Active 25d ago
Joined Mar 25, 2026