Hey Junction Box members,
A great question came up in my electrical class last night, and I thought it was worth sharing here.
Does the service disconnect have to be outside?
Under the 2023 NEC, 230.70(A)(1) permits the service disconnect outside or inside nearest the point where the service conductors enter the building, in a readily accessible location.
However, don’t stop there! Section 230.85 also requires an outdoor emergency disconnect for one- and two-family dwellings. Under the 2023 rules, that outdoor device can be the service disconnect or another permitted disconnect ahead of an indoor service disconnect.
Here’s the 2026 NEC change: 230.70(A)(1) requires the service disconnect itself to be outdoors for one- and two-family dwellings, readily accessible, on or within sight of the dwelling. Section 230.85 was deleted, and its requirements were consolidated into 230.70.
For buildings other than one- and two-family dwellings, 2026 NEC 230.70(A)(2) still permits the service disconnect outside or inside nearest the service-conductor entrance.
Remember: readily accessible is only part of the requirement. When the indoor option is permitted, the disconnect must also be nearest the point where the service conductors enter.
If you have access to both editions, compare those sections. This is a good example of why we need to check the edition, read the entire requirement, and identify the type of building involved. For actual installations, follow the edition and amendments adopted in your area.
Bonus question: When did Romex jackets change colors?
Another question came from someone who noticed that the NM cable in his older house was all white. I guessed the change happened sometime in the late 1990s. After looking it up, around 2001 is the better answer.
Manufacturers introduced the different jacket colors to make conductor sizes easier to identify. This was a manufacturer change, not an NEC-required color scheme.
The familiar colors are:
White: 14 AWG
Yellow: 12 AWG
Orange: 10 AWG
Black: larger sizes, such as 8 and 6 AWG
Southwire now also uses blue for 14/3, purple for 12/3, and pink for 10/3, while 14/2, 12/2, and 10/2 retain their familiar colors.
Older white-jacketed cable can contain different conductor sizes, so always read the cable markings to confirm the size. Color helps with identification, but the markings tell you what you have.
Thought you all would appreciate both questions. Keep the questions coming—that’s what The Junction Box is here for!
Todd